SUBJECT: M.S. Thesis Presentation
   
BY: Taylor Kunke
   
TIME: Monday, July 24, 2017, 4:00 p.m.
   
PLACE: Love Building, 210
   
TITLE: Experimental Investigation of Air-Cooled Condensers
   
COMMITTEE: Dr. Srinivas Garimella, Chair (ME)
Dr. Sheldon Jeter (ME)
Dr. Peter Loutzenhiser (ME)
 

SUMMARY

Air-cooled condensers (ACCs) offer an alternative heat rejection method for thermal power plants, reducing the required water withdrawal for conventional wet-cooled plants. However, ACCs suffer from lower efficiencies and higher capital costs compared to once-through and evaporative condensers. A heat exchanger representative of ACC geometry was manufactured and tested in a wind tunnel to quantify the thermal-hydraulic performance of an ACC at representative operating conditions. Autonomously fluttering reeds (AFRs) are installed on the air-side of these condensers and their performance is measured. The experiments showed an average of 25% enhancement in heat transfer coefficient, with a 40% increase in pressure drop due to the installation of the AFRs. The data were incorporated into a Rankine cycle power plant model, which predicted a ~0.4% cycle efficiency increase based on tradeoffs between increased fan power and lower turbine outlet pressure due to AFR enhancement.